DOWNLOAD CATALOGUE
HUBBELL PORTABLE RCD OR GFCI SPECIFICATION:
Application : Oil and Gas, Petrochemical, Utility, Fertilizer as well as other heavy industries
Electrical Ratings
Rated Voltage 120V AC, 240V AC, 120/ 240V AC,
3Ø 250V AC, 3Ø 120/ 208V AC.
Operating Voltage Range 85% to 110% .
Current Up to 30A or device rating.
Frequency 60 Hz.
Trip Level 4-6 mA.
Response Time 25 mS Max.
Dielectric Withstand 1500 VRMS across contact, 4000 VRMS between conductors and enclosure.
Surge Withstand 6000V impulse, 0.5 microseconds rise time
100kHz ringing frequency with 40% decay per cycle.
Let Go Line Voltage 60% of rated.
Power Up Manual or Automatic reset.
Environmental Ratings
Housing Rating UL Type 4X.
Construction Industrial grade design.
Type Meets UL943 Class A GFCI.
Operating Temperature -35° C to 66° C, -30° F to 150° F.